Peripheral Devices

Smoke Detectors : - 951 Series photoelectric smoke detectors

FSP-951, FSP-951-IV, FSP-951T, FSP-951T-IV, FSP-951R, FSP-951R-IV

Our photoelectric detector’s unique optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources. Intelligent (addressable) detectors include point ID capability that enable each detector address to be set with rotary address switches to provide exact detector locations. The sensitivity can be programmed using the control panel software to suit the environment. In addition, detector sensitivity is continually monitored and reported to the panel

Features & Benefits :
  • Sleek, low-profile design
  • Available in both Bright White (for new installations) and Ivory (for legacy installations)
  • Photoelectric smoke detection
  • Analog communications
  • Low standby current
  • Rotary address switches
  • Dual LEDs for 360° visibility
Specifications
  •  FSP-951/FSP-951-IV – Photoelectric smoke detection- Operating temperature: 32°F to 120°F (0°C to 49°C)
  •  FSP-951T/FSP-951T-IV – Photoelectric smoke detection with thermal detection- Operating temperature: 32°F to 100°F (0°C to 38°C)
  • FSP-951R/FSP-951R-IV – Photoelectric detection suitable for use with DNR(W) duct smoke detectors- Operating temperature: 32°F to 120°F (0°C to 49°C)
  • FSP-951, FSP-951T, FSP-951R: Available in Bright White, compatible with FlashScan® protocol systems
  • FSP-951-IV, FSP-951T-IV, FSP-951R-IV: Available in Ivory, compatible with FlashScan® and CLIP protocol systems
Listings :
  • UL Listed: S1115
  • MEA Listed: 225-02-E
  • FM Approved
  • Lloyd’s Register: 11/600013 (NFS2-640/NFS-320/NFS-320C, excluding B210LP(A))

Smoke Detectors : - 851 Series photoelectric smoke detectors

FSP-851, FSP-851T, FSP-851R

Our photoelectric detector’s unique optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources. Intelligent (addressable) detectors include point ID capability that enable each detector address to be set with rotary address switches to provide exact detector locations. The sensitivity can be programmed using the control panel software to suit the environment. In addition, detector sensitivity is continually monitored and reported to the panel.

Features & Benefits :
  • Photoelectric smoke detection
  • Analog communications
  • Low standby current
  • Rotary address switches
  • Dual LEDs for 360° visibility
Specifications
  • FSP-851 – Photoelectric smoke detection Operating temperature: 32°F to 120°F (0°C to 49°C)
  • FSP-851T – Photoelectric smoke detection with thermal detection – Operating temperature:
  •  32°F to 100°F (0°C to 38°C)
  •  FSP-851R – Photoelectric detection suitable for use with DNR(W) duct smoke detectors- Operating temperature: 32°F to 120°F (0°C to 49°C)
  • Rotary address switches for point identification and quick installation
  • Dual LEDs for 360° visibility
Listings:
  • UL Listed: S1115.
  • MEA Listed: 225-02-E .
  • FM Approved
  •  Lloyd’s Register: 11/600013 (NFS2-640/NFS-320/NFS-320C, excluding B210LP(A))

Heat Detectors : - 951 Series Thermal heat detectors

FST-951, FST-951-IV, FST-951H, FST-951H-IV, FST-951R, FST-951R-IV

NOTIFIER 951 Series Intelligent Plug-In Thermal Detectors with integral communication provides features that surpass conventional devices

 Intelligent (addressable) detectors with point ID capability that enable each detector address to be set with rotary address switches to provide exact detector locations. Our thermal detectors use an innovative thermistor sensing circuit to produce 135°F fixed, rate-of-rise and 190°F high- temperature detection for cost-effective, intelligent property protection.

Features & Benefits :
  • Sleek, low-profile design
  • Thermal smoke detection
  • Analog communications
  • Low standby current
  • Rotary address switches
  • Dual LEDs for 360° visibility 
Specifications
  • FST-951/FST-951-IV: Fixed Temperature Thermal Detector

          o Operating Temperature: –4°F to 100°F (–20°C to 38°C)

  • FST-951R/FST-951R-IV: Rate-of-Rise Thermal Detector

          o Operating Temperature: –4°F to 100°F (–20°C to 38°C)

  •  FST-951H/FST-951H-IV: High Temperature Thermal Detector

          o Operating Temperature: –4°F to 150°F (–20°C to 66°C)

          o Rotary address switches

          o Dual LEDs for 360° visibility

  • FST-951, FST-951H, FST-951R: Available in Bright White, compatible with FlashScan® protocol systems
  • FST-951-IV, FST-951H-IV, FST-951R-IV: Available in Ivory, compatible with FlashScan® and CLIP protocol systems
Listings :
  • UL Listed: S747
  • MEA Listed: 383-02-E
  • FM Approved
  • Lloyd’s Register: 11/600013 (NFS2-640/NFS-320/NFS-320C, excluding B210LP(A))

Heat Detectors : - 851 Series Thermal heat detectors

FST-851, FST-851R, FST-851H

Intelligent (addressable) detectors with point ID capability that enable each detector address to be set with rotary address switches to provide exact detector locations. Our thermal detectors use an innovative thermistor sensing circuit to produce 135°F fixed, rate-of-rise and 190°F high temperature detection for cost-effective, intelligent property protection.

Features & Benefits :
  • Thermal smoke detection
  • Analog communications
  • Low standby current
  • Rotary address switches
  • Dual LEDs for 360° visibility
Specifications
  • FST-851 Fixed Temperature Thermal Detector- Operating Temperature:  –4°F to 100°F (–20°C to 38°C)
  • FST-851R Rate-of-Rise Thermal Detector- Operating Temperature: –4°F to 100°F (–20°C to 38°C)
  • FST-851H High Temperature Thermal Detector- Operating Temperature: –4°F to 150°F (–20°C to 66°C)
  • Rotary address switches
  • Dual LEDs for 360° visibility
Listings :
  • UL Listed: S747
  • MEA Listed: 383-02-E
  • FM Approved
  • Lloyd’s Register: 11/600013 (NFS2-640/NFS-320/NFS-320C, excluding B210LP(A)) 

Manual call point - NBG-12LX :-

The Notifier NBG-12LX Notifier Manual Call Point is a state-of-the-art, dual-action pull station that includes an addressable interface for any Notifier intelligent control panel except Fire Warden series panels, and the NSP25 panel. Because the NBG-12LX is addressable, the control panel can display the exact location of the activated manual station. This leads fire personnel quickly to the location of the alarm.

Features : –
  • Maintenance personnel can open station for inspection and address setting without causing an alarm condition.
  • Built-in bicolour LED, which is visible through the handle of the station, flashes in normal operation and latches steady red when in alarm.
  • Handle latches in down position and the word “ACTIVATED “appears to clearly indicate the station has been operated.
  • Captive screw terminals wire-ready for easy connection to SLC loop (accepts up to 12 AWG/3.25 mm² wire).
  • Can be surface mounted (with SB-10 or SB-I/O) or semi flush mounted. Semi-flush mount to a standard single gang, double-gang, or 4″ (10.16 cm) square electrical box.
  • Smooth dual-action design.• Meets ADAAG controls and operating mechanisms guidelines (Section 4.1.3[13]); meets ADA requirement for 5 lb. Maximum activation force.
  • Highly visible.
  • Attractive shape and textured finish.
  • Key reset.
  • Includes Braille text on station handle.
  • Optional trim ring (BG12TR).
  • Meets UL 38, Standard for Manually Actuated Signalling Boxes.
  • Up to 99 NBG-12LX stations per loop on CLIP protocol loops.
  • Up to 159 NBG-12LX stations per loop on FlashScan® protocol loops.
  • Operating Voltage- 24 VDC , Maximum SLC loop Voltage- 28 VDC Max SLC Standby Current- 375 A, Alarm Current – 5 mA
  • Dual-color LED blinks green to indicate normal on FlashScan® systems.

MHR1 SYS-ST Honeywell System Horn Strobes

MHR1 SYS-ST Honeywell System Horn Strobes devices shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 24 volts. 24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts. Devices operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 75 and 115 cd. The devices shall not operate on a coded power supply. Horn-strobe and strobe devices shall have built in synchronization capability. Upon initial power up the devices shall be synchronized for up to 30 minutes. MHR1 SYS-ST Honeywell System Horn Strobes devices shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 24 volts. 24-volt- rated notification appliance circuit outputs shall operate between 17 and 33 volts. Devices operatebetween 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 75 and 115 cd. The devices shall not operate on a coded power supply. Horn-strobe and strobe devices shall have built in synchronization capability. Upon initial power up the devices shall be synchronized for up to 30 minutes.

Features :-
  • Three field selectable candela settings: 15, 75, and 115
  • Easy to use rotary dials for selection of candela and horn settings
  • Built in synchronization feature keeps strobes in sync for up to 30 minutes
  • Horn settings on the horn strobe model include high and low volume, continuous or temporal 3 tone
  • Round trim ring available for ceiling mount applications
  • Trim plate allows mini horn to mount to a variety of backboxes
  • Fit aesthetically with the horn strobe and strobe
Scroll to top